Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2014 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/15/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/15/2014 | MECHANICAL - FINAL | Denied | PROVIDE A TRAP IN CONDENSATE BUILT PER T FRAME SPECS. PROVIDE INSTALL INSTRUCTIONS. BLOCK & CLAMP PVC EVERY 4'. USE PRESSURE TREATED OR REDWOOD. TERMINATE CONDENSATE TO AN APPROVED LOCATION. USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE. 40 AMP FUSES DO NOT MEET THE MIN OVERCURRENT REQUIREMENT. MARK THE UNIT DATA PLATE FOR HEAT STRIP & FUSE ACCORDINGLY. PROVIDE A BUSHING IN THE ELEC DISCONNECT. SUPPORT THE ELEC CONDUIT ON ROOF. CIRCUIT BREAKER DOES NOT MEET THE MIN CIRCUIT AMPACITY. |