Permit: T14CM00139

Parcel: 12801005H

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/28/2014 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/28/2014 MECHANICAL - FINAL Approved AIR BALANCE & BACKFLOW CERTS ARE OK
05/19/2014 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
05/19/2014 MECHANICAL - FINAL Partial Approval PROVIDE A LANYARD AT CHAR BROILER. INTERLOCK MAKEUP AIR WITH EXHAUST FANS. 3 COMPARTMENT SINK TO DRAIN SEPARATELY INTO FLOOR SINK. PROVIDE BACKFLOW CERTS. PLANS SHOW ALL WATER LINES INSULATED. PROVIDE PANEL SCHEDULE. REPAIR BROKEN CONDUIT AT EXHAUST FAN & REINSTALL GREASE RECEPTORS & DRAINS.