Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T14CM00139
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2014 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
05/29/2014 | PLUMBING - FINAL | Approved | STERILIZATION REPORT OK | |
05/19/2014 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* | |
05/19/2014 | PLUMBING - FINAL | Partial Approval | PROVIDE A LANYARD AT CHAR BROILER. INTERLOCK MAKEUP AIR WITH EXHAUST FANS. 3 COMPARTMENT SINK TO DRAIN SEPARATELY INTO FLOOR SINK. PROVIDE BACKFLOW CERTS. PLANS SHOW ALL WATER LINES INSULATED. PROVIDE PANEL SCHEDULE. REPAIR BROKEN CONDUIT AT EXHAUST FAN & REINSTALL GREASE RECEPTORS & DRAINS. |