Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T14CM00135
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/14/2014 | PLUMBING - FINAL | Approved | ||
01/10/2014 | PLUMBING - FINAL | Not ready for Inspection | 1. Gas piping not connected to existing. Note: Only SW gas allowed to turn gas on and off at corp. stop. Connect to existing- SW Gas needs to make sure 3/4" supply at meter is adequete to handle 180,000 BTUs. and to test their regulator after you turned it off. UV protect armaflex. Note: taping is not an accepted method of UV protection. |