Permit: T14CM00135

Parcel: 124032290


Addresses:

1648 E 7TH ST #01


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T14CM00135

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/14/2014 PLUMBING - FINAL Approved
01/10/2014 PLUMBING - FINAL Not ready for Inspection 1. Gas piping not connected to existing. Note: Only SW gas allowed to turn gas on and off at corp. stop. Connect to existing- SW Gas needs to make sure 3/4" supply at meter is adequete to handle 180,000 BTUs. and to test their regulator after you turned it off. UV protect armaflex. Note: taping is not an accepted method of UV protection.