Permit: T14CM00129

Parcel: 12616250A


Addresses:

4154 E BROWN WY

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/15/2014 PLUMBING - FINAL Approved IVRS - Inspection :*
01/15/2014 PLUMBING - FINAL Approved CORRECTIONS HAVE BEEN MADE. PLEASE REMOVE THE OLD GAS RISER AT METER PRIOR TO CALLING GAS COMPANY.
01/13/2014 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
01/13/2014 PLUMBING - FINAL Not ready for Inspection 1. PRESS TEST OK
2. GAS PIPING NOT PROPERLY BONDED (SEE NOTES)
3. PVC NOT TO BE USED FOR T & P DRAIN
4. HORIZONTAL PIPE SUPPORT NOT TO EXCEED 10'
**NOTES: BOND GAS TO WATER AT WATER HEATER**