Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2014 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/22/2014 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 01/22/2014 | ELECTRIC - SERVICE UPGRADE | Partial Approval | CALL FOR FINALS WHEN WORK IS COMPLETE | |
| 01/17/2014 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/17/2014 | ELECTRIC - SERVICE UPGRADE | Denied | 1. RISER CONDUIT BRACE MUST BE A LISTED - HOME MADE OUT OF EMT CONDUIT NOT APPROVED 2. GROUND RODS NEED TO BE 6' MIN APART |