Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM00045
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2014 | FIRE - FINAL | Approved | ||
09/11/2014 | FIRE - FINAL | Partial Approval | Temp of C of O for stocking only NO SALES, NO PUBLIC 1. In marketing show windows need to keep grill 18" below sprinkler head or remove grill. 2. Note in storage room need to post signs stating the "KEEP STOCK 18 INCHES BELOW SPRINKLER HEADS" 3 to 4 inch letters on a contrasting background. 3. Need suite numbers posted 3" inch size |
|
09/10/2014 | FIRE - FINAL | Denied | 1. Correct coverage on main floor and storage room all was shown to Kazal Fire 2. Need to test duct smokes A/C unit could not be turned on, if city inspector for mechanical tested and passed to smoke then have copy of paperwork to show. |