Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2015 | FIRE SPKLR - FINAL | Approved | ||
| 05/05/2015 | FIRE SPKLR - FINAL | Denied | 1. Janitor closet walls don't go to deck upright coverage need throughout or add drop ceiling or finish walls to deck. 2. Remove ground wire off of riser per NFPA section 10.6.8 2010ED 3. Add sprinkler coverage in riser room have walls finished to deck or add drop ceiling 4. Label riser room door RISER ROOM 5. Need F.D. key box for riser room door |