Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T14BU01300

Parcel: 12810069C


Addresses:

436 S WILLIAMS BL


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T14BU01300

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/13/2015 FIRE SPKLR - FINAL Approved
05/05/2015 FIRE SPKLR - FINAL Denied 1. Janitor closet walls don't go to deck upright coverage need throughout or add drop ceiling or finish walls to deck.
2. Remove ground wire off of riser per NFPA section 10.6.8 2010ED
3. Add sprinkler coverage in riser room have walls finished to deck or add drop ceiling
4. Label riser room door RISER ROOM
5. Need F.D. key box for riser room door