Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T14BU01285
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/20/2016 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
11/04/2015 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Hydro passed on the stand pipe, levels 0,1,2,3,5,6,9,10 and 11 only. Restest: 4, 7, & 8 1. replace painted heads at top of level 4 elevator lobby 2. 8th floor needs dry cabinet installed,finish head installation, need as builts for changes: around steel anchors and under soffit 3. All plumbing and electric shaft heads are blocked by headache plate which drops 22 inches from the grate above - both shafts - each level ( 0-8) |
|
08/18/2015 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | BASE BUILDING GALVANIZED AREA OK AND ENTIRE BASE RISER AND TOWER SYSTEMS OKAY FOR HYDRO. |