Permit: T14BU01161

Parcel: 124040760


Addresses:

1509 E 2ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/01/2015 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/26/2015 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/06/2015 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/06/2015 MECHANICAL - FINAL Denied THE APPLIANCES DO NOT FIT UNDER THE HOOD WITH THE REQUIRED 6" OVERHANG BEYOND THE COOKING SURFACE OF THE APPLIANCES. THE MAKEUP AIR IS NOT INTERLOCKED WITH THE EXHAUST FAN. PROVIDE ACCESS TO THE ROOF