Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/01/2015 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/26/2015 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/06/2015 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/06/2015 | MECHANICAL - FINAL | Denied | THE APPLIANCES DO NOT FIT UNDER THE HOOD WITH THE REQUIRED 6" OVERHANG BEYOND THE COOKING SURFACE OF THE APPLIANCES. THE MAKEUP AIR IS NOT INTERLOCKED WITH THE EXHAUST FAN. PROVIDE ACCESS TO THE ROOF |