Inspection History Details
Inspection Status: Partial Approval
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2015 | FIRE - KITCHEN EXH HOOD FINAL | Partial Approval | 1. Tested operations of the new fixed hood system all passed. Only one problem the approved plans did not show back shelves over stoves they measured 12" out 20" above stove to the top of the shelf. According to Amerex's book states the shelves cannot be more than 11" out and 20" above the stove to the bottom of the shelf. Cintas talked to the owner and they agreed to remove the shelves. 2. Need to get mechanical final approved before fire final will be given |