Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2015 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/25/2015 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/25/2015 | MECHANICAL - FINAL | Denied | HARD WIRE EXHAUST FAN. NO CORD OR PLUG ALLOWED. INTERLOCK EXHAUST FAN WITH MAKEUP AIR UNIT. PROVIDE A RATED GASKET BETWEEN FAN AND CURB. PROVIDE A GREASE RECEPTOR AT FAN | |
| 07/09/2015 | MECHANICAL - FINAL | Denied | PROVIDE A TYPE I EXHAUST FAN | |
| 07/07/2015 | MECHANICAL - FINAL | Denied | PLEASE SCHEDULE YOUR INSPECTION WHEN SOMEONE CAN BE HERE AT 8AM PROVIDE ACCESS TO ROOF ALSO |