Permit: T14BU01034

Parcel: 13315299A

Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
02/17/2015 FIRE - KITCHEN EXH HOOD FINAL Approved Salamander was removed
Broiler was moved out from under the old salamander shelf so nozzles can properly cover the broiler.
All electrical shut down
01/14/2015 FIRE - KITCHEN EXH HOOD FINAL Denied 1. All electrical under hood shall shut down when hood extinguisher system activates
2. Need to check coverage for the salamander on plans state 36" x 24" on site 24" x 44" will need to have paperwork showing proper nozzle.