Inspection History: FIRE SPKLR - FINAL

Permit Number - T14BU01030

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/25/2015 FIRE SPKLR - FINAL Approved
02/23/2015 FIRE SPKLR - FINAL Denied 1. In shell space upright heads on every other line is 8 feet away from wall need to get head within 7' 6" from wall.
2. Over double doors entrance into shell area in hallway upright sprinkler heads blocked by insulation need to get the insulation 1" or off the sprinkler head.
3. In the main storage room by the water treat room wall upright heads to close need 4 inches or away from wall.
4. In electrical room (exposed area) there is two heads, one upright new install and one pendent that looks like its paint they are too close to each other min of 6 inches apart is needed or remove one head.
02/13/2015 FIRE SPKLR - FINAL Denied 1. Need to move sprinkler head away from truss.