Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T14BU00985

Parcel: 110120990


Addresses:

2650 N WYATT DR


Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T14BU00985

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2015 FIRE - KITCHEN EXH HOOD FINAL Approved APPROVED
AS BUILDS SUBMITTED AND APPROVED.
NOW TWO NOZZLES OVER 4 BURNER RANGE, WITH N2LP NOZZLES AT CORRECT DISTANCES. LARGER TANK HAS 20 FLOW POINTS AND 19 ARE BEING USED.
05/14/2015 FIRE - KITCHEN EXH HOOD FINAL Cancelled Per Carl, cancel because they are not ready for inspection.
05/13/2015 FIRE - KITCHEN EXH HOOD FINAL Denied Correct coverage over the 4 burner grill, size on plan shows 28"x36" what is on site is 33"x26" on the approved plan shows N1LP nozzle cannot cover. Western states will be changing the coverage to using two N2LP nozzles.
Need new plans showing changes for coverage and changes in the nozzle and flow points' schedule - please bubble areas that are changed.
03/02/2015 FIRE - KITCHEN EXH HOOD FINAL Denied 1. All electrical outlets and equipment under the hood system shall shut down when system is activated - when compliance testing was done the electrical failed to shut done.
2. Adjust nozzles to proper height and aiming point to equipment per manufacture requirements:
a. 4 burner range nozzle to height and nozzle not pointed to center
b. Tilting skillet - nozzles not properly installed per approved plans, nozzles need to be away from cover lid and nozzles centered to appliance per manufacture requirements.
3. More nozzles were added than what is on approved plans:
a. Duct on plans state 10"x 10" when it's 23" X 23", 2 red nozzles installed not 1
b. Plenum 11' 6" plans show 1 blue nozzle on each side, 2 blue nozzles are install on both sides on site.
When this was done the total nozzle points on site is now 16 the tank is 15 points therefore system is not adequate.
4. Will need as bults showing what is on site.
5. Need to check the nozzle coverage for the duct work again approved plans show 10"x10" when it's 23"x23".
6. The K-class fire extinguisher is mounted 6' above floor finish needs to be min 4" to max 5' above floor finish (to top of extinguisher).
01/08/2015 FIRE - KITCHEN EXH HOOD FINAL Denied 1. Western States had no way of testing flow.
12/24/2014 FIRE - KITCHEN EXH HOOD FINAL Denied 1. Siemens unaware of testing. Need to reschedule.