Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2015 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/20/2015 | MECHANICAL - FINAL | Denied | 1. PROVIDE HINGE KIT AT E.F. 2. FAN DISCHARGE TO BE MIN 40" ABOVE ROOF AND 10' AWAY OR 3' ABOVE MVA INTAKE 3. MVA TO BE 10' FROM ALL EXHAUST & VENT OUTLETS 4. DOUBLE LUGGING AT DISCONNECT NOT ALLOWED 5. GREASE DUCT NOT TO CODE |
|
| 12/05/2014 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/22/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/22/2014 | MECHANICAL - FINAL | Denied | 1.DUCT IS TO BE WELDED TO HOOD, UNABLE TO VERIFY CHASE ENCLOSURE(IF ANY), UNABLE TO ACCESS ROOF TO COMPLETE INSPECTION, MAKE UP AIR NOT FUNCTIONAL, HOOD APPEARS TO BE CODE COMPLIANT |