Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2014 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/12/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/12/2014 | MECHANICAL - FINAL | Denied | 1. GREASE RECEPTOR IS TO BE REMOVABLE FOR CLEANING 2. EXHAUST FAN TO BE ON A HINGE KIT ALLOW FOR CLEANING OF DUCT WORK 3. GREASE HAS NOT BEEN CLEANED FROM ROOF 4. ANY FURTHER FAILED INSPECTION WILL RESULT IN THIS PERMIT BEING RE-FEE |
|
| 10/15/2014 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/15/2014 | MECHANICAL - FINAL | Partial Approval | 1. INTERLOCK OK 2. PROVIDE LADDER FOR ROOF ACCESS |
|
| 09/11/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/11/2014 | MECHANICAL - FINAL | Denied | INTERLOCK MAKE UP AIR WITH EXHAUST FAN. FAN CANNOT BE CORD AND PLUGGED. PROVIDE A GREASE RECEPTOR AT FAN. PROVIDE A CURB THAT FITS THE EXHAUST FAN. CLEAN GREASE OFF OF ROOF |