Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date |
Description |
Inspector |
Results |
Comments |
| 12/08/2014 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Approved |
200 PSI for 2 hours APPROVED |
| 08/12/2014 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Denied |
Piping placement okay wire tracer in place, plastic wrap on mag-lugs, all nuts broken off mag-lugs - okay to bury still needs 200 psi test for 2 hours and flushed. |