Permit: T14BU00885

Parcel: 125100730

Inspection Status: Approved

Inspection History: POOL/SPA BONDING GRID

Permit Number - T14BU00885

Inspection Description - POOL/SPA BONDING GRID

Inspection Status - Approved

Date Description Inspector Results Comments
08/29/2014 POOL/SPA BONDING GRID Approved MAKE CONNECTIONS AT GRID
08/25/2014 POOL/SPA BONDING GRID Partial Approval 1. BONDING GRID MUST BE 12-24 INCHES OUTSIDE OF POOL ALONG PERIMETER.
2. PROVIDE FOUR CONNECTION POINTS TO REBAR CAGE. 3. EXTEND GROUNDING TO PUMP MOTOR.