Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2014 | FIRE SPKLR - FINAL | Approved | CORRECTIONS MADE | |
| 09/08/2014 | FIRE SPKLR - FINAL | Denied | 1. North building riser room replace missing cover plate for flow switch 2. North building Group room #109 correct sprinkler coverage 10' off one wall and 9 foot off another wall 3. South building open room # 241 sprinkler head to far off wall 8' 4. South building closet # 244 cover on sprinkler head |