Permit: T14BU00878

Parcel: 12212001A


Addresses:

4689 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T14BU00878

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/02/2015 FIRE - KITCHEN EXH HOOD FINAL Approved Cut link and tested pull station gas did shut down -PASSED
11/24/2014 FIRE - KITCHEN EXH HOOD FINAL Denied Gas failed to shut down valve needs to be replaced, still need to test cut link.
10/27/2014 FIRE - KITCHEN EXH HOOD FINAL Cancelled Cancelled by Armor according to the installer the makeup air failed to shut down and no separation plate between the deep fryer and 10 burner stove.