Permit: T14BU00878

Parcel: 12212001A


Addresses:

4689 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T14BU00878

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/29/2014 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/21/2014 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/21/2014 MECHANICAL - FINAL Denied THE MAKEUP AIR UNIT HAS BEEN DISCONNECTED. MAKEUP AIR MUST BE INTERLOCKED WITH EXHAUST FAN. THE FAN DOES NOT PROPERLY FIT THE CURB & THE CURB HAS A WOODEN RISER THAT MUST BE REMOVED. YOU WILL NEED A CURB ADAPTOR SO THE FAN FITS PROPERLY. PROVIDE A GREASE RECEPTOR AT EXHAUST FAN. PROVIDE THE MISSING GREASE CUP AT HOOD. PROVIDE A DISCONNECT AT FAN. THE HOOD & GREASE DUCT ARE OK.