Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T14BU00877
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/03/2014 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
09/08/2014 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
09/08/2014 | MECHANICAL - FINAL | Partial Approval | THE DUCT FROM THE FAN TO THE RISER NEEDS TO BE 16 GAUGE ALSO. THE CLEANOUT NEEDS TO BE ATTACHED WITH ROD & WING NUTS |
|
08/14/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/13/2014 | MECHANICAL - FINAL | Denied | THE HOOD AND EXHAUST FAN MEET TYPE I REQUIREMENTS. HOWEVER, THE DUCT FROM THE HOOD TO THE FAN IS NOT TYPE I, 16 GAUGE WELDED STEEL DUCT. THIS DUCT WILL NEED TO BE REPLACED OR REPLACE STOVE WITH A TYPE II APPLIANCE |