Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2014 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
| 10/20/2014 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1. Need as bults showing back shelf on range 3' X 10 ½" and correct nozzle position for proper coverage under shelf. 2. Need links set up as per approved plans 3. Nozzle for deep fryers to high need to correct height 4. Need to test pull station cable failed apart was not able to test it. We did cut a lik and make up air did shut down and gas did shut down. |