Permit: T14BU00876

Parcel: 11105026F

Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
11/18/2014 FIRE - KITCHEN EXH HOOD FINAL Approved
10/20/2014 FIRE - KITCHEN EXH HOOD FINAL Denied 1. Need as bults showing back shelf on range 3' X 10 ½" and correct nozzle position for proper coverage under shelf.
2. Need links set up as per approved plans
3. Nozzle for deep fryers to high need to correct height
4. Need to test pull station cable failed apart was not able to test it.
We did cut a lik and make up air did shut down and gas did shut down.