Permit: T14BU00874

Parcel: 11101035C


Addresses:

3800 E RIVER RD


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T14BU00874

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/09/2015 FIRE - ALARM FINAL Approved Tested ( smoked) 8 ground floor detectors and 3 upper level detectors. One detector on second floor was not accessible and did not get smoked.
All alarms reported to the monitoring company as supervisory - with a note not to dispatch a fire response.
01/20/2015 FIRE - ALARM FINAL Denied 1. All building duct detectors need to be addressed as Supervisory Alarms. Currently they come in as General Alarms.