Inspection History Details
Inspection Status: Partial Approval
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T14BU00865
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/23/2014 | FIRE - KITCHEN EXH HOOD FINAL | Partial Approval | 1. Tested hood with Wildcat. 2. Still need Mechanical work and final. |
|
09/22/2014 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1. There are a shelf's blocking both ranges that measures 11 ½ inches therefore nozzles are blocked, need to resubmit plans showing shelves and proper way to cover ranges. 2. Tighten piping to nozzles so as the piping to nozzles cannot move making aiming points incorrect. |