Permit: T14BU00865

Parcel: 117140890


Addresses:

375 S STONE AV


Inspection Status: Partial Approval

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T14BU00865

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
10/23/2014 FIRE - KITCHEN EXH HOOD FINAL Partial Approval 1. Tested hood with Wildcat.
2. Still need Mechanical work and final.
09/22/2014 FIRE - KITCHEN EXH HOOD FINAL Denied 1. There are a shelf's blocking both ranges that measures 11 ½ inches therefore nozzles are blocked, need to resubmit plans showing shelves and proper way to cover ranges.
2. Tighten piping to nozzles so as the piping to nozzles cannot move making aiming points incorrect.