Permit: T14BU00863

Parcel: 13817047B


Addresses:

301 E LOS REALES RD


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T14BU00863

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/10/2015 FIRE SPKLR - FINAL Approved
11/25/2015 FIRE SPKLR - FINAL Denied 1. South and North nurseries bathrooms head over 10 feet of wall need to correct distance to 7.5 to 9 feet off wall
2. Mechanical room south and north wall need all upright coverage within 12 inches of deck
3. North air handler room head blocked by light
4. Off south room vacuum room head blocked by light.
5. Need a 12 head spare head sprinkler box