Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T14BU00863
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2015 | FIRE SPKLR - FINAL | Approved | ||
| 11/25/2015 | FIRE SPKLR - FINAL | Denied | 1. South and North nurseries bathrooms head over 10 feet of wall need to correct distance to 7.5 to 9 feet off wall 2. Mechanical room south and north wall need all upright coverage within 12 inches of deck 3. North air handler room head blocked by light 4. Off south room vacuum room head blocked by light. 5. Need a 12 head spare head sprinkler box |