Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T14BU00863
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2015 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
| 08/17/2015 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | All piping for placement done still needs to Hydro at 200 PSI for hours. - Changed from AP to PA to allow for reinspection per Ken B. |
|
| 08/03/2015 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Only looked at overhead piping and placement for areas marked on approved plans no pressure test was done. | |
| 06/12/2015 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Only looked at overhead /courtesty inspection of what will be enclosed in hard deck where band/choir and pulpit area are. There were two heads added in an alcove behind pulpit in hydro calced area. Must resubmit drawings for approval. Asbuilds must reflect changes to riser ( 2 90 degree angles added before the main rise) must reflect the change in the 1 1/4 inch pipe that now comes off lower branch to supply band storage room. reflect any 90's to avoid duct work . |