Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/13/2014 |
FIRE - KITCHEN EXH HOOD FINAL |
|
Approved |
Tested hood no electrical to shut down, gas did shut down, 1 pull station, nozzles location, types, heights, coverage and link cut all passed. One K-class fire extinguisher in place. No alarm system therefore no monitoring system for the hood. |