Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T14BU00815
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/05/2014 | FIRE - ALARM FINAL | Approved | ||
08/04/2014 | FIRE - ALARM FINAL | Partial Approval | Temp C of O OKAY for stocking and training NO PUBLIC OR SALES 1. Per approved plans need horn/strobe installed in both outside patios. 2. Need to have sound system shut down when fire alarm actives 3. All duct smokes shall be set up as supervisory signal not alarm activation. |