Date Description Inspector Results Comments
08/05/2014 FIRE - ALARM FINAL Approved
08/04/2014 FIRE - ALARM FINAL Partial Approval Temp C of O OKAY for stocking and training NO PUBLIC OR SALES
1. Per approved plans need horn/strobe installed in both outside patios.
2. Need to have sound system shut down when fire alarm actives
3. All duct smokes shall be set up as supervisory signal not alarm activation.