Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date |
Description |
Inspector |
Results |
Comments |
| 10/07/2014 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Approved |
200 psi for 2 hours |
| 10/06/2014 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Denied |
Was not pressured up but I did look over placement piping size; need to add sprinkler coverage in riser room. Just need to add head and pressure up 200 psi for 2 hours. |