Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2014 | FIRE - ALARM FINAL | Approved | ||
| 10/09/2014 | FIRE - ALARM FINAL | Denied | Need to test 2nd duct smoke on main dinning floor | |
| 10/08/2014 | FIRE - ALARM FINAL | Denied | Duct smoke in kitchen passed Panel fried when checking wiring for the ansul system that did not sound alarm system |
|
| 10/06/2014 | FIRE - ALARM FINAL | Denied | 1. Need ansul tested 2. Duct smoke in kitchen failed to work All duct smokes on dinning floor PASSED x 3 |
|
| 10/03/2014 | FIRE - ALARM FINAL | Cancelled |