Inspection History: FIRE - ALARM FINAL
Permit Number - T14BU00763
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2014 | FIRE - ALARM FINAL | Approved | ||
| 07/31/2014 | FIRE - ALARM FINAL | Denied | 1. all testing for portables has been approved. However the main fire alarm pannel is located in the main school building. Simplex did an annual inspection and found none of the duct detectors are working and the batteries need to be replaced. 2. We need an annual fire alarm report showing no deficiencies before I will approve the fire alarm. |
|
| 07/24/2014 | FIRE - ALARM FINAL | Denied | Tested all smokes, horns/strobes, missing devices, low battery, power off and groung fault all passed. What failed was he signals never got to the monitoring company. Need to lock the breker in the on postion in the panel. |