Permit: T14BU00763

Parcel: 13305054M


Addresses:

8711 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T14BU00763

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2014 FIRE - ALARM FINAL Approved
07/31/2014 FIRE - ALARM FINAL Denied 1. all testing for portables has been approved. However the main fire alarm pannel is located in the main school building. Simplex did an annual inspection and found none of the duct detectors are working and the batteries need to be replaced.

2. We need an annual fire alarm report showing no deficiencies before I will approve the fire alarm.
07/24/2014 FIRE - ALARM FINAL Denied Tested all smokes, horns/strobes, missing devices, low battery, power off and groung fault all passed.

What failed was he signals never got to the monitoring company.
Need to lock the breker in the on postion in the panel.