Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T14BU00724

Parcel: 12709011E


Addresses:

101 N WILMOT RD


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T14BU00724

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/23/2015 FIRE - ALARM FINAL Approved Received letter from Alltech Security stating corrections are completed. Below is an e-mail corresponds actual letter on file in FMRS.
E-mail:
Hi Carl,
Yes we did add the module to send a signal when the Fire pump was put in the off position. WE tested the DB level of the 4th Floor again after the center horn/strobe was replaced. All areas we now above 20Db higher than ambient noise level. All other floors were above the required Db level on the first inspection. Please let me know if you need any other information and if I need to take any other action to get this permit approved & closed.
Thank You
Fabian Aparisi
Alltech Security
520-747-3600
11/20/2014 FIRE - ALARM FINAL Partial Approval This permit was pulled for replacing an old fire alarm panel that they could not get parts for, all other devices such as horns/strobes, tamper, water flow, fire pump stayed the same. Approved plans state this is a class "A" wiring but when tested with wiring take apart on the first floor we lost all devices on other floors make this a class "B" wiring therefore will need to wire alarm system to a class "A" or will need as bults showing system is wired as a class "B".

Tested pulls, smokes, tampers and water flows passed.

Two problems did show up - a switch in the fire pump control panel was put into the off position and nothing showed on the alarm panel we almost left the property with the pump off. 2nd problem was on 4th floor could not hear the horns with ear plugs in need to complete a decibel test on all floors and make sure the following is met in IFC 907.5.2.1.1 :
Average sound pressure. The audible alarm notification appliances shall provide a sound pressure level of 15 decibels (dBA) above the average ambient sound level or 5 dBA above them maximum sound level having a duration of a least 60 seconds, whichever is greater, in every occupiable space within the building.