Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T14BU00722

Parcel: 125101400


Addresses:

3455 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T14BU00722

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
09/23/2014 FIRE SPKLR - OH PIPING & HYDRO Approved
08/26/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Kitchen entry add or move head to far off wall 8' 6"
2. Under trellis dining area by kitchen entry add head coverage head to far off wall
3. Above coolers coverage needs to be corrected add heads closer to the pitch but keep heads 6' apart and 4" away from plywood wall add more heads to the north end.
08/20/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval OKAY to close up ceilings
Check overhangs in Lou of insulation they cover areas with sprinklers need to change plans to reflect what's on site.
Still need to see above loading dock area.
Kitchen area was corrected
08/13/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval OKAY TO COVER CEILING MAIN FLOORS
200 PSI TEST FOR 2 HOURS APPROVED
1. Need as builts for changes on approved sprinkler plans bubble all changes on plans and why changes were made.
a. In dining room pendants were to be used but now changed to sidewalls x 6.
b. Upright coverage southwest corner above kitchen hood dead pocket space need to add a head.
c. Correct sprinkler coverage above coolers Westside missing one upright head.
d. Correct requirements for the eaves completely fill with insulation or add proper sprinkler coverage.
2. Need to see upright coverage in loading dock area, all covered up by plywood.