Permit: T14BU00715

Parcel: 205943650

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T14BU00715

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/16/2014 FIRE SPKLR - FINAL Approved
10/15/2014 FIRE SPKLR - FINAL Denied 1. Remove protective cover construction cap on sprinkler head and install proper cover plate in 2nd floor closet northeast corner.
2. Need lock on breaker to fire bell -*LOCK OUT NOT NEED PER NFPA 13D 2010ED SEC 7.6 as long as the home has interconnected smoke alarm install per NFPA 72 standards.