Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T14BU00702
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/31/2014 | FIRE - KITCHEN EXH HOOD FINAL | Approved | plans are in nozzles corrected, fire extinguishers in place | |
07/29/2014 | FIRE - KITCHEN EXH HOOD FINAL | Denied | Need as built for changes on plans need to bubble all changes on plans and call out what was done, redo flow points for all changes. Change out all seals on nozzles and use proper lube. Install 4 K class fire extinguishers in kitchen 2 for the proper coverage of all appliances under the hoods and 2 are needed for the amount of oil in the deep fryers totaling of 120 pounds. |