Permit: T14BU00702

Parcel: 12801005H

Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T14BU00702

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2014 FIRE - KITCHEN EXH HOOD FINAL Approved plans are in nozzles corrected, fire extinguishers in place
07/29/2014 FIRE - KITCHEN EXH HOOD FINAL Denied Need as built for changes on plans need to bubble all changes on plans and call out what was done, redo flow points for all changes.
Change out all seals on nozzles and use proper lube.
Install 4 K class fire extinguishers in kitchen 2 for the proper coverage of all appliances under the hoods and 2 are needed for the amount of oil in the deep fryers totaling of 120 pounds.