Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T14BU00681

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/25/2014 FIRE - KITCHEN EXH HOOD FINAL Approved
07/23/2014 FIRE - KITCHEN EXH HOOD FINAL Denied 1. Gas failed to shut down IFC904.11.2
2. Make up air failed to shut down IFC904.11.2
3. Failed to report to FACP IFC904.3.5
Only tested the pull station need to cut a link also
All nozzles are correct
07/03/2014 FIRE - KITCHEN EXH HOOD FINAL Not ready for Inspection Just call in to ask questions about where to install pull station I did approved to install pull station 10 feet way in kitchen next to double sink on the 6 inch wall