Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T14BU00681
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/25/2014 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
07/23/2014 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1. Gas failed to shut down IFC904.11.2 2. Make up air failed to shut down IFC904.11.2 3. Failed to report to FACP IFC904.3.5 Only tested the pull station need to cut a link also All nozzles are correct |
|
07/03/2014 | FIRE - KITCHEN EXH HOOD FINAL | Not ready for Inspection | Just call in to ask questions about where to install pull station I did approved to install pull station 10 feet way in kitchen next to double sink on the 6 inch wall |