Permit: T14BU00670

Parcel: 14041075A

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
11/18/2014 FIRE - ALARM FINAL Approved Payment made
10/23/2014 FIRE - ALARM FINAL Denied Can not final out permit until payment is made.
Clean agent system and fire alarm tested the following per approved plans:
1. Dampers closing - PASSED
2. Pull station - PASSED
3. Abort switch - PASSED
4. By-pass switch - PASSED
5. Four smokes - PASSED
6. Horn/strobe - PASSED
7. Firing time 30 sec. - PASSED
8. Ceiling clipped down - PASSED
9. Walls sealed - PASSED
10. Door sealed - PASSED
11. Signals to main panel and monitor company - PASSED
12. Hydro for piping - PASSED
13. Piping placement - PASSED
14. Clean agent tank brace tie down - PASSED