Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2014 | FIRE - ALARM FINAL | Approved | Payment made | |
| 10/23/2014 | FIRE - ALARM FINAL | Denied | Can not final out permit until payment is made. Clean agent system and fire alarm tested the following per approved plans: 1. Dampers closing - PASSED 2. Pull station - PASSED 3. Abort switch - PASSED 4. By-pass switch - PASSED 5. Four smokes - PASSED 6. Horn/strobe - PASSED 7. Firing time 30 sec. - PASSED 8. Ceiling clipped down - PASSED 9. Walls sealed - PASSED 10. Door sealed - PASSED 11. Signals to main panel and monitor company - PASSED 12. Hydro for piping - PASSED 13. Piping placement - PASSED 14. Clean agent tank brace tie down - PASSED |