Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T14BU00650
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/25/2014 | FIRE - ALARM FINAL | Approved | Horn/strobes added in the 4 conferences rooms - passed 2 Smokes moved 36" away from vents in electrical rooms -passed All duct smokes tested by the city mechanical inspector Jim Buige - Passed thank you JIM! |
|
09/24/2014 | FIRE - ALARM FINAL | Denied | 1. Need to keep smoke detectors 36" away from intake or exhaust vents correct smokes in the electrical room rooms 1st floor 2. Add visual strobes in conference room on 2nd floor per approved plans 3. Need to test all duct smokes or have paperwork from City Of Tucson mechanical inspector showing testing was completed and passed. 4. Need certificate from the monitoring company showing they are UL/FM approved for monitoring fire equipment. |