Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T14BU00639
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2015 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
04/02/2015 | MECHANICAL - FINAL | Approved | CORRECTIONS HAVE BEEN MADE | |
03/09/2015 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
03/09/2015 | MECHANICAL - FINAL | Partial Approval | NEW EXHAUST FAN MUST BE HARD WIRED | |
08/15/2014 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
08/15/2014 | MECHANICAL - FINAL | Partial Approval | UPON FURTHER INVESTIGATION, IVE DETERMINED THE FRONT HOOD DUCT IS NOT WELDED 16 GAUGE STEEL. THERE IS A RATED SHAFT IN THE ATTIC. THE GREASE DUCT CAN BE REPLACED AND G CLEAN OUT IS NOT REQUIRED, FIRE WRAP NOT REQUIRED RECOMMENDED 3 CONTRACTORS ANY PENETRATION INTO THE NEW DUCT WITH FIRE SUPPRESSION PIPING MUST BE DONE WITH LIQUID TIGHT FITTINGS |
|
07/01/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/01/2014 | MECHANICAL - FINAL | Denied | BOTH GREASE DUCTS DO NOT MEET TYPE I REQUIRMENT DUCTS ARE TO BE 16 GA WELDED WITH NO FASTNER. THE HOOD IN BACK KITCHEN, FAN & RELATED DUCT WORK DO NOT MELT TYPE I REQUIRMENTS THE FAN FOR FRONT HOOD HAS BEEN ALTERATED DOES NOT FIT THE CURB, UNSAFE ELEC, ETC. THERE IS NO INTERLOCK WITH MAKE UP AIR THE HOOD IN FRONT KITCHEN IS THE ONLY PORTION THAT MEETS TYPE REQUIRMENTS |