Permit: T14BU00639

Parcel: 10714257E


Addresses:

14 W GRANT RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T14BU00639

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/02/2015 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/02/2015 MECHANICAL - FINAL Approved CORRECTIONS HAVE BEEN MADE
03/09/2015 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
03/09/2015 MECHANICAL - FINAL Partial Approval NEW EXHAUST FAN MUST BE HARD WIRED
08/15/2014 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
08/15/2014 MECHANICAL - FINAL Partial Approval UPON FURTHER INVESTIGATION, IVE DETERMINED THE FRONT HOOD DUCT IS NOT WELDED 16 GAUGE STEEL. THERE IS A RATED SHAFT IN THE ATTIC. THE GREASE DUCT CAN BE REPLACED AND G CLEAN OUT IS NOT REQUIRED, FIRE WRAP NOT REQUIRED
RECOMMENDED 3 CONTRACTORS
ANY PENETRATION INTO THE NEW DUCT WITH FIRE SUPPRESSION PIPING MUST BE DONE WITH LIQUID TIGHT FITTINGS
07/01/2014 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/01/2014 MECHANICAL - FINAL Denied BOTH GREASE DUCTS DO NOT MEET TYPE I REQUIRMENT DUCTS ARE TO BE 16 GA WELDED WITH NO FASTNER. THE HOOD IN BACK KITCHEN, FAN & RELATED DUCT WORK DO NOT MELT TYPE I REQUIRMENTS THE FAN FOR FRONT HOOD HAS BEEN ALTERATED DOES NOT FIT THE CURB, UNSAFE ELEC, ETC. THERE IS NO INTERLOCK WITH MAKE UP AIR THE HOOD IN FRONT KITCHEN IS THE ONLY PORTION THAT MEETS TYPE REQUIRMENTS