Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2015 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/11/2015 | MECHANICAL - FINAL | Denied | 1. TYPE 1 DUCT NOT INSPECTED @ INSTALL. NEED TO LEAK TEST & INSPECT ARC (?) WRAP 2. ANY FURTHER FAILED INSPECTIONS WILL REQUIRE A RE-FEE |
|
| 09/11/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/11/2014 | MECHANICAL - FINAL | Denied | THE GREASE DUCT IS NOT TYPE I. THERE IS NO MAKE UP AIR.THERE IS NO DISCONNECT AT EXHAUST FAN. THERE IS NO GREASE RECEPTOR AT THE FAN. PROVIDE LANYARDS AT FRYERS. PROVIDE A PERMIT FOR THE NEW A/C UNIT ON ROOF & BRING UP TO CURRENT CODES | |
| 08/20/2014 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/15/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/15/2014 | MECHANICAL - FINAL | Denied | 1. NO ROOF ACCESS PROVIDED 2. CONTRACTOR TO BE ON SITE PROVIDE CONTACT NAME AND NUMBER |