Permit: T14BU00530

Parcel: 127035470

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T14BU00530

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2014 FIRE - ALARM FINAL Approved
07/14/2014 FIRE - ALARM FINAL Denied 1. Need to add duct detectors to alarm system.
2. Need to add all smoke/fire dampers to alarm system
3. Need to caulk all boxes for strobes/horn boxes and holes in walls that are fire rated.
4. Needs as built bubble areas where changings were made on plans and show a new matrix schedule on plans.