Permit: T14BU00514

Parcel: 12801005H

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T14BU00514

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2014 FIRE SPKLR - FINAL Approved Corrections made
09/10/2014 FIRE SPKLR - FINAL Denied Correct coverage on main floor and storage room all was shown to Kazal Fire
Add sprinkler coverage in closet by cashers
Back storage room 1st piler blocking sprinkler coverage
Soffit or 4' feet needs sprinkler coverage added
Soffits with heads over 1/2 distances away from center line on soffit need to add head coverage.