Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T14BU00407

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/22/2014 FIRE - KITCHEN EXH HOOD FINAL Approved
05/15/2014 FIRE - KITCHEN EXH HOOD FINAL Partial Approval Hood system need to be monitored
Need resubmittals on plans showing how equipment is located under hood and piping of nozzles
04/21/2014 FIRE - KITCHEN EXH HOOD FINAL Denied Plans do reflect what is on site missing one deep fryer and no oven in place duct work is 10" x 22" and other one is 10 ½" X 22", one grill is smaller and nozzle was changed out also will need to have the system monitored. Need as bults to show what is under the hood and all nozzles match.