Permit: T14BU00377

Parcel: 13313005F

Inspection Status: Closed

Inspection History: FIRE SPKLR - FINAL

Permit Number - T14BU00377

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Closed

Date Description Inspector Results Comments
10/07/2022 FIRE SPKLR - FINAL Closed CONTRACTOR DID NOT CALL IN PERMIT TO COMPLETE FINAL INSPECTION. PERMIT CLOSED WITHOUT FINAL INSPECTION.
10/23/2014 FIRE SPKLR - FINAL Denied 1. East stairwell painted head bottom floor.
2. East entrance on north side new door way was installed ruined the sprinkler coverage more than 7ft 6 inch
3. All tape needs to be removed from heads for final.
4. 2nd story room aka drama room has a painted in the sophet.
5. Exit sign is blocking sprinkler coverage 2nd floor sw stairwell.
6. damaged deflector in room 205 look on main set of plans on site to locate this room #.