Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T14BU00316
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
11/14/2014 | MECHANICAL - FINAL | Denied | PROVIDE HINGE KIT AND GREASE CATCH FOR EXHAUST FAN 506.53, 506.5.2 EXHAUST FAN AND MAKE-UP AIR SHALL BE CONTROLLED BY ONE SWITCH, SO THAT PROPER VENTALAZATION IS PROVIDED IN BLDG 508.1 IMC | |
09/29/2014 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
09/29/2014 | MECHANICAL - FINAL | Not ready for Inspection | PROVIDE ROOF ACCESS MAKE-UP AIR AND EXHAUST FAN ARE REQUIRED TO BE INTER LOCKED |