Permit: T14BU00269

Parcel: 11901074A


Addresses:

310 E BENSON HY

Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
08/25/2014 FIRE - KITCHEN EXH HOOD FINAL Approved ELECTRICAL SHUT DOWN
07/01/2014 FIRE - KITCHEN EXH HOOD FINAL Denied All electrical appliances under hood shall shut down upon activation, when testing the pull station the electric oven and bread proofer failed to shut down owner is using outlets outside of the hood system.
Inspection was done on the following:
1. Nozzles correct
2. Nozzle height correct
3. Hood nozzles correct
4. Plenum nozzles correct
5. Main tank 6 gallon correct
6. Pull station placement correct