Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2014 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ELECTRICAL SHUT DOWN | |
| 07/01/2014 | FIRE - KITCHEN EXH HOOD FINAL | Denied | All electrical appliances under hood shall shut down upon activation, when testing the pull station the electric oven and bread proofer failed to shut down owner is using outlets outside of the hood system. Inspection was done on the following: 1. Nozzles correct 2. Nozzle height correct 3. Hood nozzles correct 4. Plenum nozzles correct 5. Main tank 6 gallon correct 6. Pull station placement correct |