Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2014 | FIRE SPKLR - FINAL | Approved | ||
| 07/03/2014 | FIRE SPKLR - FINAL | Partial Approval | fire pump test passed. still need to run pump when alarm is hooked up and test all tampers. |
|
| 07/02/2014 | FIRE SPKLR - FINAL | Denied | 1. fire pump installed backwards. |