Permit: T14BU00116

Parcel: 10511061Q


Addresses:

4420 N STONE AV


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T14BU00116

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2015 FIRE - ALARM FINAL Approved
06/25/2014 FIRE - ALARM FINAL Denied 1. Need dedicated circuit for power to fire alarm, no sharing with music equipment.
2. Label breaker number and location of panel inside fire alarm box.
3. IFC 907.5.2.1 Audible Alarms
Audible alarm notification appliances shall be provide and emit a distinctive sound that is not to be used for any purpose other than that of a fire alarm.
1. Cannot share sounder with burglar alarm