Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2015 | FIRE - ALARM FINAL | Approved | ||
| 06/25/2014 | FIRE - ALARM FINAL | Denied | 1. Need dedicated circuit for power to fire alarm, no sharing with music equipment. 2. Label breaker number and location of panel inside fire alarm box. 3. IFC 907.5.2.1 Audible Alarms Audible alarm notification appliances shall be provide and emit a distinctive sound that is not to be used for any purpose other than that of a fire alarm. 1. Cannot share sounder with burglar alarm |